Hava Giris Sicakligi °C
Hava Ozgul Agirligi Kg/³m/Specific Weighttofair kg/³m
Z Katsayisi/Z Coefficient
Sicak su icin/For hot water
Buhar icin/For Steam
Kaynar su icin/For HTH Water
90/70 °C
0.1 ATU
0.3 ATU
0.5 ATU
1 ATU
2 ATU
2.5 ATU
3 ATU
4 ATU
6 ATU
110/80 °C
130/90 °C
150/110 °C
160/120 °C
22
20
18
15
10
5
0
1.197
1.205
1.213
1.226
1.248
1.270
1.293
0.86
0.97
1.00
1.03
1.12
1.19
1.28
0.95
0.98
1.00
1.05
1.13
1.21
1.28
0.098
1.04
1.06
1.10
1.18
1.28
1.34
1.02
1.08
1.13
1.16
1.24
1.32
1.41
1.12
1.18
1.24
1.26
1.29
1.43
1.51
1.32
1.37
1.38
1.42
1.48
1.56
1.66
1.37
1.42
1.44
1.48
1.54
1.62
1.73
1.42
1.47
1.49
1.53
1.59
1.68
1.79
1.52
1.57
1.60
1.64
1.71
1.81
1.92
1.68
1.73
1.76
1.81
1.87
1.97
2.07
0.76
0.82
0.84
0.82
0.92
0.97
1.02
0.93
0.98
1.00
1.03
1.08
1.13
1.17
1.12
1.20
1.22
1.25
1.30
1.35
1.39
1.29
1.32
1.34
1.38
1.43
1.48
1.52
ADA TYPE HEATER
Sýcak Hava Üniteleri
Tavan Tipi Üniteleri
Duvar Tipi Üniteleri
Aparey Seçimi
 
 
 
 
 
 
 
 
 
Capacities given in the table 2 are valid for fixed conditions. To find out the capacities for different conditions Z Coefficients shown in table 3 shall be used
Q: Rated heating capacity (kcal/h) Table 2
tg: Temperature of the inlet air ( C )
Q: Heating capacity under
operating conditions (kcal/h)
Z: Coefficients Table 3
Selection examples
Example 1: selection of an ADA Unit Heater providing 56.000 Kcal/h
by 10 C inler air for 90/70 C hot water installation
Step 1- For 90/70 C hot water temperature and 10 C inlet air tempe
rature Z isdetermined as 1,12 from table 3
Step 2-
By applying the formula Q = Q the result is Q =56.000 =50.000 Kcal/h Z 1,12
Selection of the appropriate unit heater type from Table 2 is as follows
Selected unit heater type : ADA 50
Approx water preasure drop : 580 mm SS (mm WG)
Motor power :1 PS
Example 2: The selection of a unit heater supplying 24.000 kcal/h by
Using 30 % external air wiht 150/110 C H.T.H.W installation will be as follow in Istanbul, room temperature is selected as 20 C and outside
air temperature at 3 C
a: tj = room temperature ( C )
td = outside temperature ( C )
tg = temperature of the inlet air ( C )
tg = 0,30 (3) + 0,70(20) 0 13,1 C C
b: for 150/110 C H.T.H.W and 13,1 C air inlet temperature Z is determined as 1,269 from table 3 by interpolation
Q = Q = 24.000 = 18912 kcal/h Z 1,269
for H.T.H.W system the suitable unit type is selected from table 2 as indicated below.
Selected UNIT type = ADA 16
Approx.water presure drop = 44 mm SS
Motor power = 1/3 HP
Also for % fresh air adjustment there must be inside fresh air mixing box